Siemens LMO14 Diagnostics Control Box Part No: LMO14.113C2E, LMO14.111.C2EM

Replaces / supersedes: LMO14.113C2E

  • Siemens LMO14.111C2 diagnostics control box
  • Suitable for Bentone burners
  • Tested and approved in accordance with DIN EN 298 
  • Under-voltage detection 
  • Electrical remote reset
  • Bridging contact for oil preheater
  • Timer for oil preheater 
  • Accurate and reproducible control sequence thanks to digital signal handling
  • Controlled intermittent operation after 24 hours of continuous operation
  • Multicolor indication of fault status and operational status messages

Read more product details …

Delivered: 1 - 2 working days (Ireland, Mainland EU)

67.64 55.90 exc VAT

25 in stock

This Siemens LMO14.111C2 Control Box (220/240v) fits the Bentone range of Oil Burners/Boilers. LMO control boxes are used to start and control 1 or 2 stage blown burners with intermittent feed.

    Control Box is suitable for:

  • Liquid burners with fans according to EN 267
  • Oil burners of monoblock construction according to EN 230 
  • LMO44 for use with stationary air heaters
  • Under-voltage detection 
  • Possibility of remote electric restart 
  • Shunt contact for fuel oil heater
  • Time control for the oil heater 

Specification

Part Number
LMO14.113C2E, LMO14.111.C2EM
Replaces / Supersedes
LMO14.113C2E
Voltage
AC 230 V
Burner power
<30 kg / h
Remote reset
tw max
5 s
t1 / t1´ min
15/16 s
TSA max
10 s
t3 min
15 s
t3n max
3 seconds
t4 min
-
Comparable LOA type ...
LOA24.173A27

Package Contents

1 x Siemens LMO14 Diagnostics Control Box.

Manuals / Datasheets